Learning Advanced Features
Operates when auto restart fails (Pr. 08–09)
OU.31 Relay1 Set relay output (Relay 1).
OU.33 Q1 Define
Select output for multi-function output terminal (Q1). Q1 is open collector TR
output.
OU.53 TripOut On Dly,
OU.54 TripOut OffDly
If a fault trip occurs, trip relay or multi-function output operates after the time
delay set in OU.53. Terminal is off with the input initialized after the time delay
5.35.3 Multi-function Output Terminal Delay Time Settings
Set on-delay and off-delay times separately to control the output terminal and relay operation
times. The delay time set at codes OU.50–51 applies to multi-function output terminal (Q1) and
relay (Relay 1), except when the multi-function output function is in fault trip mode.
OU
50
Multi-function output
On delay
DO On Delay 0.00
0.00–100.00
s
51
Multi-function output
Off delay
DO Off Delay 0.00
0.00–100.00
s
52
Select multi-function
output terminal
DO NC/NO Sel 00*
00–11
bit
* Displayed as on keypad.
Output Terminal Delay Time Setting Details
OU.52 DO NC/NO Sel
Select terminal type for relay and multi-function output terminal. An additional
three terminal type selection bits at the terminal block will be added when an
expansion I/O is added. By setting the relevant bit to 0, it will operate A terminal
(Normally Open), and setting it to 1 will operate B terminal (Normally Closed).
Shown below in the table are Relay 1 and Q1 settings starting from the right bit.