8.7 Output Terminal Block Function group (PAR→OU)
In the following table, the data shaded in grey will be displayed when a related code has been
selected.
SL: Sensorless vector control (dr.09) , I – IM Sensorless, P – PM Sensorless
*O/X: Write-enabled during operation, 7/L/A: Keypad/LCD keypad/Common
Code
Name LCD Display Setting Range
Property*
V/F SL Ref.
01 0h1601
Analog
output 1 item
AO1 Mode
0:Freque
ncy
O/A O
I/P
p.192
02 0h1602
AO1 Gain -1000.0-1000.0(%) 100.0 O/A O I/P
p.192
03 0h1603
AO1 Bias -100.0-100.0(%) 0.0 O/A O I/P
p.192
04 0h1604
AO1 Filter 0-10000(ms) 5 O/A O I/P
p.192
05 0h1606
constant
AO1
Const %
0.0-100.0(%) 0.0 O/A O
I/P
p.192
06 0h1606
output 1
AO1
Monitor
0.0-1000.0(%) 0.0 -/A O
I/P
p.192
30 0h161E
Fault output
item
Trip Out
Mode
010
50
O/A O
I/P
p.201 1 Low voltage
50
The initial value 0010 will be displayed on the keypad as .