86
Learning Basic Features
Use caution when operating the inverter with Power-on Run enabled as the motor will begin rotating
when the inverter starts up.
4.9 Reset and Restart
Reset and restart operations can be setup for inverter operation following a fault trip, based on the
terminal block operation command (if it is configured). When a fault trip occurs, the inverter cuts
off the output and the motor will free-run. Another fault trip may be triggered if the inverter
begins its operation while motor load is in a free-run state.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Operation
drv
Command source
Cmd
Source*
1
2
Fx/Rx-1 or
Fx/Rx-2
0–5
-
Pr
08
Reset restart setup
RST Restart
1
Yes
0–1
09
No. of auto restart
Retry
Number
0
010
10
Auto restart delay time
Retry Delay
1.0
060
sec
* Displayed under DRV-06 in an LCD keypad.
Note
To prevent a repeat fault trip from occurring, set Cn.71 (speed search options) bit 2 equal to 1. The
inverter will perform a speed search at the beginning of the operation.
If the speed search is not enabled, the inverter will start its operation in a normal V/F pattern and
accelerate the motor. If the inverter has been turned on without reset and restart enabled, the
terminal block command must be first turned off, and then turned on again to begin the inverters
operation.