RS-485 Communication Features
Output communication
address x
Input communication
address x
Currently Registered CM Group Parameter
Address Parameter Assigned content by bit
0h0100-0h0107
Status Parameter-1-
Status Parameter-8
Parameter communication code value registered at CM.31-38
(Read-only)
0h0110-0h0117
Control Parameter-8
Parameter communication code value registered at CM.51-58
(Read/Write access)
When registering control parameters, register the operation speed (0h0005, 0h0380, 0h0381) and
operation command (0h0006, 0h0382) parameters at the end of a parameter control frame. For
example, when the parameter control frame has 5 parameter control items (Para Control - x), register
the operation speed at Para Control-4 and the operation command to Para Control-5.
7.3 Communication Protocol
The built-in RS-485 communication supports LS INV 485 and Modbus-RTU protocols.
7.3.1 LS INV 485 Protocol
The slave device (inverter) responds to read and write requests from the master device (PLC or PC).
Request
Normal Response