8.10 Protection Function group (PAR→Pr)
In the following table, the data shaded in grey will be displayed when a related code has been
selected.
SL: Sensorless vector control (dr.09) , I – IM Sensorless, P – PM Sensorless
*O/X: Write-enabled during operation, 7/L/A: Keypad/LCD keypad/Common
Code
Name LCD Display Setting Range
V/F SL Ref.
00 - Jump Code Jump Code 1-99 40 O/A O I/P p.48
04 0h1B04
Load level
setting
Load Duty
0 Normal Duty
1:Heavy
Duty
X/A O I/P p.208
1 Heavy Duty
05 0h1B05
Input/output
open-phase
protection
Phase Loss
Chk
00-11
00
62
X/A O I/P p.213
01
Output
open phase
10
Input open
phase
06 0h1B06
Input voltage
range during
open-phase
IPO V Band 1-100(V) 15 X/A O I/P p.213
07 0h1B07
Deceleration
time at fault trip
Trip Dec
Time
0.0-600.0(s) 3.0 O/A O I/P -
08 0h1B08
Selection of
startup on trip
reset
RST Restart
0 No
0:No O/A O I/P p.174
1 Yes
09 0h1B09
Number of
automatic
restarts
Retry
Number
0-10 0 O/A O I/P p.174
10
63
0h1B0A
restart
Retry Delay 0.0-60.0(s) 1.0 O/A O I/P p.174
62
The initial value 0000 will be displayed on the keypad as .
63
Displayed when Pr.09 is set higher than 0.