Table of Functions
301
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property
*
V/F SL Ref.
12 0h1B0C
Motion
at speed
command loss
Lost Cmd
Mode
0 None
0:None O/A O I/P p.216
1 Free-Run
2 Dec
3 Hold Input
4 Hold Output
5 Lost Preset
13
64
0h1B0D
Time to decide
speed
command loss
Lost Cmd
Time
0.1-120(s) 1.0 O/A O I/P p.216
14
64
0h1B0E
Operation
frequency
at speed
command
loss
Lost Preset F
Start frequency-
Maximum
frequency(Hz)
0.00 O/A O I/P p.216
15
64
0h1B0F
Analog input
loss decision
level
AI Lost Level
0 Half x1
0:Half of
x1
O/A O I/P p.216
1 Below x1
17 0h1B11
Overload
warning
selection
OL Warn
Select
0
No
0:No O/A O I/P p.208
1 Yes
18 0h1B12
Overload alarm
level
OL Warn
Level
30-180(%) 150 O/A O I/P p.208
19 0h1B13
Overload
warning time
OL Warn
Time
0.0-30.0(s) 10.0 O/A O I/P p.208
20 0h1B14
Motion at
overload fault
OL Trip
Select
0
None
1:Free-
Run
O/A O I/P p.208
1
Free-Run
2 Dec
21 0h1B15
Overload fault
level
OL Trip Level 30-200(%) 180 O/A O I/P p.208
22 0h1B16
Overload fault
time
OL Trip Time 0.0-60.0(s) 60.0 O/A O I/P p.208
25 0h1B19
Underload
warning
selection
UL Warn Sel
0 No
0:No O/A O I/P p.219
1 Yes
26 0h1B1A
Underload
warning time
UL Warn
Time
0.0-600.0(s) 10.0 O/A O I/P p.219
64
Displayed when Pr.12 is not set to 0 (NONE).

Table of Contents