The inverter produces output voltage proportional to 2
square of the operation frequency. This setup is ideal for
variable torque loads such as fans or pumps.
4.13.3 User V/F Pattern Operation
The S100 inverter allows the configuration of user-defined V/F patterns to suit the load
characteristics of special motors.
bA
07 V/F pattern V/F Pattern 2 User V/F
0–3
-
41 User Frequency1 User Freq 1 15.00
0–
Maximum
Hz
43 User Frequency2 User Freq 2 30.00
0–
Maximum
Hz
45 User Frequency3 User Freq 3 45.00
0–
Maximum
Hz
47 User Frequency4 User Freq 4
Maximum
frequency
0–
Maximum
Hz
User V/F pattern Setting Details
bA.41 User Freq 1–
bA.48 User Volt 4
Set the parameter values to assign arbitrary frequencies (User Freq 1–4) for start
and maximum frequencies. Voltages can also be set to correspond with each
frequency, and for each user voltage (User Volt 1–4).