Learning Basic Features
Code
Description
3
Square2
The inverter produces output voltage proportional to 2
square of the operation frequency. This setup is ideal for
variable torque loads such as fans or pumps.
4.13.3 User V/F Pattern Operation
The S100 inverter allows the configuration of user-defined V/F patterns to suit the load
characteristics of special motors.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
bA
07 V/F pattern V/F Pattern 2 User V/F
03
-
41 User Frequency1 User Freq 1 15.00
0
Maximum
frequency
Hz
42
User Voltage1
User Volt 1
25
0100
%
43 User Frequency2 User Freq 2 30.00
0
Maximum
frequency
Hz
44
User Voltage2
User Volt 2
50
0100
%
45 User Frequency3 User Freq 3 45.00
0
Maximum
frequency
Hz
46
User Voltage3
User Volt 3
75
0100
%
47 User Frequency4 User Freq 4
Maximum
frequency
0
Maximum
frequency
Hz
48
User Voltage4
User Volt 4
100
0100%
%
User V/F pattern Setting Details
Code
Description
bA.41 User Freq 1
bA.48 User Volt 4
Set the parameter values to assign arbitrary frequencies (User Freq 14) for start
and maximum frequencies. Voltages can also be set to correspond with each
frequency, and for each user voltage (User Volt 1–4).