Linear V/F Pattern Setting Details
dr.18 Base Freq
Sets the base frequency. A base frequency is the inverter’s output frequency
when running at its rated voltage. Refer to the motor’s rating plate to set this
dr.19 Start Freq
Sets the start frequency. A start frequency is a frequency at which the inverter
starts voltage output. The inverter does not produce output voltage while the
frequency reference is lower than the set frequency. However, if a deceleration
stop is made while operating above the start frequency, output voltage will
continue until the operation frequency reaches a full-stop (0Hz).
4.13.2 Square Reduction V/F pattern Operation
Square reduction V/F pattern is ideal for loads such as fans and pumps. It provides non-linear
acceleration and deceleration patterns to sustain torque throughout the whole frequency range.
bA 07 V/F pattern V/F Pattern
0–3 -
Square Reduction V/F pattern Operation - Setting Details
bA.07 V/F Pattern
Sets the parameter value to 1(Square) or 3(Square2) according to the load’s start
characteristics.
The inverter produces output voltage proportional to 1.5
square of the operation frequency.