RS-485 Communication Features
229
7 RS-485 Communication Features
This section in the user manual explains how to control the inverter with a PLC or a computer over
a long distance using the RS-485 communication features. To use the RS-485 communication
features, connect the communication cables and set the communication parameters on the
inverter. Refer to the communication protocols and parameters to configure and use the RS-485
communication features.
7.1 Communication Standards
Following the RS-485 communication standards, S100 products exchange data with a PLC and
computer. The RS-485 communication standards support the Multi-drop Link System and offer an
interface that is strongly resistant to noise. Please refer to the following table for details about the
communication standards.
Item
Standard
Communication method/
Transmission type
RS-485/Bus type, Multi-drop Link System
Inverter type name
S100
Number of connected
inverters/ Transmission
distance
Maximum of 16 inverters / Maximum1,200m (recommended distance:
within 700m)
Recommended cable size
0.75mm², (18AWG), Shielded Type Twisted-Pair (STP) Wire
Installation type
Dedicated terminals (S+/S-/SG) on the control terminal block
Power supply
Supplied by the inverter - insulated power source from the inverters
internal circuit
Communication speed
1,200/2,400/9,600/19,200/38,400/57,600/115,200 bps
Control procedure
Asynchronous communications system
Communication system
Half duplex system
Character system
Modbus-RTU: Binary / LS Bus: ASCII
Stop bit length
1-bit/2-bit
Frame error check
2 bytes
Parity check
None/Even/Odd
7.2 Communication System Configuration
In an RS-485 communication system, the PLC or computer is the master device and the inverter is
the slave device. When using a computer as the master, the RS-232 converter must be integrated