The master/slave setting cannot be changed while the inverter is operating in slave mode.
4.23 User Sequence Setting
User Sequence creates a simple sequence from a combination of different function blocks. The
sequence can comprise of a maximum of 18 steps using 29 function blocks and 30 void
parameters.
1 Loop refers to a single execution of a user configured sequence that contains a maximum of 18
steps. Users can select a Loop Time of between 10-1,000ms.
The codes for user sequences configuration can be found in the US group (for user sequence
settings) and the UF group (for function block settings).
US
01
User sequence operation
command
User Seq Con 0 0–2 -
02
User sequence operation
time
User Loop Time 0 0–5 -
11–
Output address link1–18
Link UserOut1–
0 0–0xFFFF -
31–
Input value setting1–30 Void Para1–30
0 -9999–9999 -
80 Analog input 1
P2P In V1(-10–
10
0 0–12,000 %
88 Digital output P2P Out DO 0
0–0x03
bit
UF
01 User function 1 User Func1 0
0–28
-
02 User function input 1-A User Input 1-A 0
0–0xFFFF
-
03 User function input 1-B User Input 1-B 0
0–0xFFFF
-
04 User function input 1-C User Input 1-C 0
0–0xFFFF
-
05 User function output 1 User Output 1 0
-32767–32767
-
06 User function 2 User Func2 0
0–28
-
07 User function input 2-A User Input 2-A 0
0–0xFFFF
-
08 User function input 2-B User Input 2-B 0
0–0xFFFF
-
09 User function input 2-C User Input 2-C 0 0–0xFFFF -