Learning to Perform Basic Operations
3.3.6 Frequency Setting (Potentiometer) and Operation (Terminal
Input)
Step
Instruction
Keypad Display
1
Turn on the inverter.
-
2
Ensure that the first code of the Operation group is selected, and
the code 0.00 (Command Frequency) is displayed.
3
Press the [] key 4 times to go to the Frq (Frequency reference
source) code.
4
Press the [ENT] key.
The Frq code in the Operation group is currently set to 0 (keypad).
5
Press the [] key to change the parameter value to 2
(Potentiometer), and then press the [ENT] key.
The new parameter value will flash.
6
Press the [ENT] key once again.
The Frq code will be displayed again. The frequency input has
been configured for the potentiometer.
7
Press the [] key 4 times.
Returns to the first code of the Operation group (0.00).From here
frequency setting values can be monitored.
8
Adjust the potentiometer to increase or decrease the frequency
reference to 10Hz.
-
9
Refer to the wiring diagram at the bottom of the table, and close
the switch between the P1 (FX) and CM terminals.
The RUN indicator light flashes and the FWD indicator light comes
on steady. The current acceleration frequency is displayed.
10
When the frequency reference is reached (10Hz), open the switch
between the P1 (FX) and CM terminals.
The RUN indicator light flashes again and the current deceleration
frequency is displayed. When the frequency reaches 0Hz, the RUN
and FWD indicators turn off, and the frequency reference
(10.00Hz) is displayed again.
0.00
frq
)
@
frq
0.00