Table of Functions
271
8.4 Expanded Function group (PARAd)
In the following table, the data shaded in grey will be displayed when a related code has been
selected.
SL: Sensorless vector control (dr.09) , I IM Sensorless, P PM Sensorless
*O/X: Write-enabled during operation, 7/L/A: Keypad/LCD keypad/Common
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F SL Ref.
00
-
Jump Code
Jump Code
1-99
24
O/A
O
I/P
p.48
01 0h1301
Acceleration
pattern
Acc Pattern 0 Linear
0:
Linear
X/A O I/P p.92
02 0h1302
Deceleration
pattern
Dec Pattern 1 S-curve X/A O I/P p.92
03
13
0h1303
S-curve
acceleration
start point
gradient
Acc S Start 1-100(%) 40 X/A O I/P p.92
04
13
0h1304
S-curve
acceleration end
point gradient
Acc S End 1-100(%) 40 X/A O I/P p.92
05
14
0h1305
S-curve
deceleration
start point
gradient
Dec S Start 1-100(%) 40 X/A O I/P p.92
06
14
0h1306
S-curve
deceleration
end point
gradient
Dec S End 1-100(%) 40 X/A O I/P p.92
07 0h1307 Start Mode Start Mode
0
Acc
0:Acc X/A O I/P p.101
1
DC-Start
08
15
0h1308 Stop Mode Stop Mode
0
Dec
0:Dec X/A O I/P p.102
1
DC-Brake
2
Free-Run
4
Power
Braking
09 0h1309
Selection of
prohibited
Run Prevent
0
None
0: None X/A O I/P p.84
1
Forward
13
Displayed when Ad. 01 is set to 1 (S-curve).
14
Displayed when Ad. 02 is set to 1 (S-curve).
15
DC braking and power braking (Ad.08, stop mode options 1 and 4) are not available when dr.09
(Control Mode) is set to 6 (PM Sensorless).

Table of Contents