4.5 Command Source Configuration
Various devices can be selected as command input devices for theS100 inverter. Input devices
available to select include keypad, multi-function input terminal, RS-485 communication and field
bus adapter. If UserSeqLink is selected, the common area can be linked with user sequence output
and can be used as command.
Operation
drv Command Source Cmd Source*
0–5
-
* Displayed under DRV-06 on the LCD keypad.
4.5.1 The Keypad as a Command Input Device
The keypad can be selected as a command input device to send command signals to the inverter.
This is configured by setting the drv (command source) code to 0 (Keypad). Press the [RUN] key on
the keypad to start an operation, and the [STOP/RESET] key to end it.
Operation
drv Command source Cmd Source* 0 KeyPad 0–5 -
* Displayed under DRV-06 on the LCD keypad.
4.5.2 Terminal Block as a Command Input Device (Fwd/Rev Run
Commands)
Multi-function terminals can be selected as a command input device. This is configured by setting
the drv (command source) code in the Operation group to 1(Fx/Rx). Select 2 terminals for the
forward and reverse operations, and then set the relevant codes (2 of the 5 multi-function terminal
codes, In.65–71 for P1–P7) to 1(Fx) and 2(Rx) respectively. This application enables both terminals
to be turned on or off at the same time, constituting a stop command that will cause the inverter
to stop operation.