79
Learning Basic Features
Code
Description
[An example of a multi-step operation]
Speed
Fx/Rx
P5
P4
P3
0 - - -
1 - -
2
-
-
3
-
4
- -
5
-
6
-
7
In.89 InCheck Time
Set a time interval for the inverter to check for additional terminal block inputs
after receiving an input signal.
After adjusting In.89 to 100ms and an input signal is received at P5, the inverter
will search for inputs at other terminals for 100ms, before proceeding to
accelerate or decelerate based on P5’s configuration.