350
Maintenance
Inspection
area
Inspection item
Inspection
details
Inspection
method
Judgment
standard
Inspection
equipment
protection test?
open circuit
conditions.
Cooling
system
Cooling fan
Are any of the
fan parts loose?
Check all
connected
parts and
tighten all
screws.
No
abnormality
-
Display
Display device
Is the display
value normal?
Check the
command
value on the
display device.
Specified and
managed
values must
match.
Voltmeter,
Ammeter, etc.
10.1.3 Bi-annual Inspections
Inspection
area
Inspection
item
Inspection
details
Inspection
method
Judgment
standard
Inspection
equipment
Motor
Insulation
resistance
Megger test
(between the
input, output
and earth
terminals).
Disconnect the
cables for
terminals U/V/
W and test the
wiring.
Must be
above 5 MΩ
DC 500 V Megger
Do not run an insulation resistance test (Megger) on the control circuit as it may result in damage to the
product.
10.2 Storage and Disposal
10.2.1 Storage
If you are not using the product for an extended period, store it in the following way:
Store the product in the same environmental conditions as specified for operation (refer to 1.3
Installation Considerations on page 5).
When storing the product for a period longer than 3 months, store it between 10˚C and 30˚C,