Learning Advanced Features
195
5.34.2 Analog Pulse Output
Output item selection and pulse size adjustment can be made for the TO (Pulse Output) terminal.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
OU
33
Multi-function output 1
Q1 define
39
TO
038
-
61
Pulse output setting
TO Mode
0
Frequency
015
-
62 Pulse output gain TO Gain 100.0 -1000.01000.0 %
63
Pulse output bias
TO Bias
0.0
-100.0-100.0
%
64
Pulse output filter
TO Filter
5
010000
ms
65
Pulse output constant
output2
TO Const % 0.0 0.0-100.0 %
66
Pulse output monitor
TO Monitor
0.0
0.01000.0
%
Analog Pulse Output Setting Details
Code
Description
OU.33 Q1 Define
In case of Standard I/O, pulse output TO and multi-function output Q1 share the
same terminal. Set OU.33 to 32kHz pulse output and follow the instructions below
to make wiring connections that configure the open collector output circuit.
1. Connect a 1/4W, 560Ω resistor between VR and Q1 terminals.
2. Connect EG and CM terminals.
When wiring the resistor, a resistance of 560Ω or less is recommended to stably
provide 32kHz pulse output.
When connecting to a pulse between the S100 inverters, please connect pulse
output(Q1-EG) to pulse input(TI-CM) directly without resistor and wire.