Learning Advanced Features
• Multiple I/O< -> Multiple I/O : Connect to TO -> TI, CM -> CM
• Standard I/O <-> Standard I/O : Connect to Q1 -> P5, EG -> CM
• Multiple I/O <-> Standard I/O : Do not support.
OU.62 TO Gain,
OU.63 TO Bias
Adjusts output value and offset. If frequency is selected as an output, it will
operate as shown below.
=
× +
The following graph illustrates that the pulse output (TO) changes depend on
OU.62 (TO Gain) and OU.63 (TO Bias) values. The Y-axis is an analog output
current(0–32kHz), and X-axis is % value on output item.
For example, if the maximum frequency set with dr.20 (Max Freq) is 60Hz and
present output frequency is 30Hz, then the x-axis value on the next graph is 50%.
OU.64 TO Filter Sets filter time constant on analog output.
OU.65 TO Const %
If analog output item is set to constant, the analog pulse output is dependent on
the set parameter values.
OU.66 TO Monitor
Monitors analog output value. Displays the maximum output pulse (32kHz) as a
percentage (%) of the standard.
OU.08 AO2 Gain and OU.09 AO2 Bias Tuning Mode on 4–20mA output