Learning Advanced Features
Outputs feedback volume of a PID controller as a
standard. Outputs approximately 6.6V at 100%.
Outputs output value of a PID controller as a
standard. Outputs approximately 10V at 100%.
Outputs OU.05 (AO1 Const %) value as a standard.
OU.02 AO1 Gain,
OU.03 AO1 Bias
Adjusts output value and offset. If frequency is selected as an output item, it
will operate as shown below.
1 =
× 1 + 1
The graph below illustrates the analog voltage output (AO1) changes depend
on OU.02 (AO1 Gain) and OU.3 (AO1 Bias) values. Y-axis is analog output
voltage (0–10V), and X-axis is % value of the output item.
Example, if the maximum frequency set at dr.20 (Max Freq) is 60Hz and the
present output frequency is 30Hz, then the x-axis value on the next graph is
50%.
Set filter time constant on analog output.
OU.05 A01 Const %
If analog output at OU.01 (AO1 Mode) is set to 15(Constant), the analog
voltage output is dependent on the set parameter values (0–100%).
OU.06 AO1 Monitor
Monitors analog output value. Displays the maximum output voltage as a
percentage (%) with 10V as the standard.