Learning Advanced Features
04 Analog output1 filter AO1 Filter 5
0–10000
ms
05 Analog constant output1 AO1 Const % 0.0
0.0–100.0
%
06 Analog output1 monitor AO1 Monitor 0.0
0.0–1000.0
%
Voltage and Current Analog Output Setting Details
OU.01 AO1 Mode
Select a constant value for output. The following example for output voltage
setting.
Outputs operation frequency as a standard. 10V
output is made from the frequency set at dr.20(Max
10V output is made from 200% of inverter rated
current (heavy load).
Voltage
Sets the outputs based on the inverter output
voltage. 10V output is made from a set voltage in
bA.15 (Rated V).
If 0V is set in bA.15, 200V/400V models output 10V
based on the actual input voltages ( 240V and 480V
Outputs inverter DC link voltage as a standard.
Outputs 10V when the DC link voltage is 410Vdc for
200V models, and 820Vdc for 400V models.
Outputs the generated torque as a standard.
Outputs 10V at 250% of motor rated torque.
Monitors output wattage. 200% of rated output is
the maximum display voltage (10V).
Outputs the maximum voltage at 200% of no load
current.
Outputs the maximum voltage at 250% of rated
torque current
=
�
2
−
2
Outputs set frequency as a standard. Outputs 10V
at the maximum frequency (dr.20).
Outputs frequency calculated with Acc/Dec
function as a standard. May vary with actual output
Outputs command value of a PID controller as a
standard. Outputs approximately 6.6V at 100%.