Learning Protection Features
Under Load Trip and Warning Setting Details
Sets the underload fault trip occurs. If set to 0(None), does not detect the
underload fault trip. If set to 1 (Free-Run), the output is blocked in an
underload fault trip situation. If set to 2 (Dec), the motor decelerates and
stops when an underload trip occurs.
Sets the underload warning options. Set to 1(Yes) and set the multi-function
output terminals (at OU-31 and 33) to 7 (Underload). The warning signals are
output when an underload condition arises.
Pr.28 UL Trip Time
The protection function operates when the underload level condition
explained above is maintained for a set warning time or fault trip time. This
function does not operate if energy-saving operation is activated at Ad-50
Pr.30 UL BF Level
• Setting Heavy Duty
- Do not support Pr.29.
- At Pr.30, the underload level is decided based on the motor’s rated current.
• Setting Normal Duty
- At Pr.29, the under load rate is decided based on twice the operation
frequency of the motor’s rated slip speed (bA.12 Rated Slip).
- At Pr.30, the under load rate is decided based on the base frequency set at
dr.18 (Base Freq).An upper limit and lower limit is based on the inverter’s rated
current.