92
TI input filter time
constant
TI Filter 10 0–9999 ms
93
TI Pls x1 0.00 0.00–32.00 kHz
94
Output% at TI
minimum pulse
TI Perc y1 0.00 0.00–100.00 %
95
TI Pls x2 32.00 0.00–32.00 kHz
96
Output% at TI
maximum pulse
TI Perc y2 100.00 0.00–100.00 %
97
Invert TI direction
of rotation
TI Inverting 0 No
0–1
-
98 TI quantizing level TI Quantizing 0.04
%
* Data shaded in grey is applied only for Standard I/O.
*Quantizing is disabled if ‘0’ is selected.
TI Pulse Input Setting Details
In.69 P5 Define
In case of Standard I/O, Pulse input TI and Multi-function terminal P5 share the
same therminal.
Set the In.69 P5 Define to 54(TI).
In.01 Freq at 100%
Configures the frequency reference at the maximum pulse input. The frequency
reference is based on 100% of the value set with In.96.
• If In.01 is set to 40.00 and codes In.93–96 are set at default, 32kHz input to TI
yields a frequency reference of 40.00Hz.
•
If In.96 is set to 50.00 and codes In.01, In.93–95 are set at default, 32kHz input
to the TI terminal yields a frequency reference of 30.00Hz.
Displays the pulse frequency supplied at TI.
In.92 TI Filter
Sets the time for the pulse input at TI to reach 63% of its nominal frequency
(when the pulse frequency is supplied in multiple steps).
In.93 TI Pls x1–
In.96 TI Perc y2
Configures the gradient level and offset values for the output frequency.