73
Learning Basic Features
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
54
I2 output at minimum
current (%)
I2 Perc y1 0.00
0100
%
55
I2 maximum input
current
I2 Curr x2 20.00
0.0024.00
mA
56
I2 output at maximum
current (%)
I2 Perc y2 100.00
0.00100.00
%
61
I2 rotation direction
options
I2 Inverting 0 No
01
-
62
I2 Quantizing level
I2 Quantizing
0.04
0*, 0.0410.00
%
* Quantizing is disabled if 0’ is selected.
Input Current (I2) Setting Details
Code
Description
In.01 Freq at 100%
Configures the frequency reference for operation at the maximum current (when
In.56 is set to 100%).
If In.01 is set to 40.00Hz, and default settings are used for In.5356, 20mA
input current (max) to I2 will produce a frequency reference of 40.00Hz.
If In.56 is set to 50.00 (%), and default settings are used for In.01 (60Hz) and
In.5355, 20mA input current (max) to I2 will produce a frequency reference
of 30.00Hz (50% of 60Hz).
In.50 I2 Monitor
Used to monitor input current at I2.
In.52 I2 Filter
Configures the time for the operation frequency to reach 63% of target
frequency based on the input current at I2.
In.53 I2 Curr x1
In.56 I2 Perc y2
Configures the gradient level and off-set value of the output frequency.