User Manual Using the Software 64
Relay Setup Screen
Ref Temp: XX.X allows you to view the temperature value that is driving the function of this relay.
Note: This is a static display value, Ref Temp is calculated when you enter the “Relay Setup” screen
from the previous “Relay Status Overview” window and the value is refreshed at 1 minute intervals.
To refresh the value, you must go back to the previous screen and then reenter this screen.
NameAllows you to give the relay a descriptive title. Pressing Edit will bring up a keyboard where you
can enter an alphanumeric name.
Name Settings Screen
Relay ConfigurationAllows you to select whether the relay is Disabled, Normally Energized, or Normally
Deenergized.
Disabled keeps the relay in the Deenergized State (See Section 4.3.3 Relay Output Wiring
Figure:
Form-C Relay in Deenergized (Off) State).
Normally Energized keeps the relay in the Energized (on) state when the Restore Setpoint condition
is met (See Section 4.3.3 Relay Output Wiring
Figure: Form-C Relay in Energized (On) State). And the
relay switches to the Deenergized (off) state when the Alarm setpoint Condition is met (See Section
4.3.3
Relay Output Wiring Figure: Form-C Relay in Deenergized (Off) State). This is the failsafe mode
wherein a power outage of the LumaSmart causes the relay to act as if the Alarm Condition is met
(See Section 4.3.3
Relay Output Wiring Figure: Form-C Relay in Deenergized (Off) State).
Normally Deenergized keeps the relay in the Deenergized (off) state when the Restore Setpoint
condition is met (See Section 4.3.3 Relay Output Wiring
Figure: Form-C Relay in Deenergized (Off)
State). And the relay switches to the Energized state when the Alarm setpoint Condition is met (See
Section 4.3.3
Relay Output Wiring Figure: Form-C Relay in Energized (On) State). This is a non-failsafe
mode wherein a power outage of the LumaSMART causes the relay to act as if the Restore Condition
is met (See Section 4.3.3
Relay Output Wiring Figure: Form-C Relay in Deenergized (Off) State).