EasyManuals Logo

LumaSense LumaSMART User Manual

LumaSense LumaSMART
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #88 background imageLoading...
Page #88 background image
LumaSMART
®
User Manual Modbus Protocol Testing 88
The value was changed to 1 to specify Enabled Normally Deenergized
Register Address 85 was set to 35 (Alarm Setpoint)
Register Address 86 was set to 25 (Restore Setpoint)
Register Address 87 was set to (0000 0000 0011 1000 binary) = 56 Decimal =
only bits for channels 4, 5 and 6 were set.
Register Address 88 was set to 2 to specify ‘OR’ logic.
Additionally, the read holding register address 148 was read to ensure that
the bits for channels 4, 5, and 6 were set (make sure that the associated
input probe channels are enabled).
Checking the registers for Relay 5 shows that the desired values are stored.
You can also verify by reviewing the LumaSMART relay setup screen:
Relay Setup screen
Given the Ref Temp of 36+ °C, the relay should Energize.
Reviewing of the Modbus Coil Status also confirms that, under this condition, the relay did Energize.
Coil Status
Setting the value of register 84 to 2 Normally Energized will cause the ‘config’ of the relay to change from
‘Normally Deenergized’ to Normally ‘Energized'. The result is reflected in the Coil Status showing the relay is now
Deenergized.
Coil Status Deenergized

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LumaSense LumaSMART and is the answer not in the manual?

LumaSense LumaSMART Specifications

General IconGeneral
BrandLumaSense
ModelLumaSMART
CategoryController
LanguageEnglish