EasyManua.ls Logo

Notifier AFP-200

Notifier AFP-200
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Read Status
120 AFP-200 PN 15511:H2 10/14/2002
Read Point Status
Figure 114 shows an example of read point for a detector and Figure 115 shows an
example of read point for a module.
Detector Example For example, to read the status of a photoelectric detector at
address 13: press *, enter the address (13), then press the
ENTER key. The control panel
displays information about the detector as shown in Figure 114:
Figure 114 Detector Read Status Sample Screen
Module Example For example, to read the status of a monitor module at address
08: press #, enter the address (08), then press the
ENTER key. The control panel displays
information about the module as shown in Figure 115:
Figure 115 Module Read Status Sample Screen
NORMAL@SMOKE(PHOTO)
WEST@HALLWAY@FLR@5
Z05@ZO1@Z15@Z87@Z90
0.15/1.00%@DPV08@D13
Type Code
Custom Label for
the detector
CBE selections
for the detector
Current detector reading of
percent of alarm (15% of 1.0
equals 0.15% per foot (30.48
cm) obscuration).
Address (01-99)
Detector sensitivity selection (See
Appendix G “Pre-Alarm
(AWACS™) Applications”.)
Current status of the detector (NORMAL,
ALARM, TROUBL, or DISABL)
D (detector); if not a detector: M
(module), Z (zone), or B (panel circuit)
Alarm Verification count showing the
detector entered the verification cycle eight
times since the counter was last cleared.
Alarm Verification selection enabled; if not
enabled (*).
Pre-Alarm enabled (if not enabled (*).
Drift compensation enabled;
if not enabled (*).
PROGRM@CONTROL
MODULE@ADDRESS@08
Z00@Z@@Z@@Z@@Z
@@@@@@@@@@@@@S*M08
“M” (Module) identifies the type
of device
Default zone selection is
Z00 (general alarm)
Walk Test (*) is not selected by
default. (To select, change to “W”)
Type Code (For explanations, refer to
Table 23 on page 82)
Custom label for
this device
CBE selections
Two-digit address (01-99)
Silenceable (S) selected by default.
(* = not selected). Required selection
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFP-200

Related product manuals