Addressable Modules System Overview
AFP-200 PN 15511:H2 10/14/2002 23
Monitor Modules: FMM-1, FZM-1, FMM-101.
Addressable modules used to monitor conventional initiating
devices. Use the FMM-1 for normally open contact alarm
initiating devices, such as manual pull stations, four-wire
smoke detectors, heat detectors, waterflow, security contacts,
and supervisory devices. Use the FZM-1 for specific two-wire
smoke detectors in addition to normally open contacts. Wire
supervised circuits as NFPA Style B or Style D circuits. Use
the FMM-101 when mounting directly in the electrical box of
the device being monitored; this smaller package is limited to
Style B circuits only and does not include a blinking LED or a
magnetic test switch.
Relay Module. FRM-1 serves as a Form-C control relay. It
resembles an FCM-1 and also comes with a thermoplastic
cover for mounting to a 4-inch (10.16 cm) square mounting
box.
XP5-C Modules. XP5-C Modules allow the AFP-200 to
control a maximum of five individual circuits. These modules
can be configured as NACs/telephone or relay circuits. Their
function is similar to that of the control or relay modules
described above.
XP5-M Modules. XP5-M Modules allow the AFP-200 to
monitor a maximum of five individual circuits. Their function
is similar to those of the monitor modules described above.
Loop Isolator Module (ISO-X). The ISO-X module is an
automatic switch that opens the circuit voltage to a
communications loop branch(es) whenever a fault is detected
on that circuit. The remainder of the communications loop
leading up to the ISO-X continues to operate, unaffected by the
fault.
NBG-12LX. A dual action addressable manual pull station
featuring a key-lock reset. The pull station includes a
mini-monitor module and responds to an address set with
built-in rotary decimal switches.
NBG-12LRA. A dual-action agent release station featuring an
abort switch, release LED, normal LED, and a key-lock reset.
The release station includes a mini-monitor module and
responds to an address set with built-in rotary decimal
switches.
8
9
10
11
12
13
14
150
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
TENS
ONES
LOOP
LOOP ADDRESS
ADDRESS
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
ONES
8
9
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
FMM-1.cdr
0
10
11
12
13
14
15
ADDRESS
LOOP
1
2
3
4
TENS
ONES
6
7
8
9
5
0
1
2
3
4
6
7
8
9
5
FMM-101.cdr
FMM-1, FZM-1
FMM-101
8
9
8
8
9
9
10
11
12
13
14
15
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
0
1
2
3
4
7
6
5
TENS
ONES
ADDRESS
LOOP
FMM-1.cdr
FRM-1
SYSTEM
NORM AL
SYSTEM
A
CTIVATED
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFP-200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-200 and is the answer not in the manual?

Notifier AFP-200 Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
Auxiliary Power Output24 VDC, 500 mA
Operating Temperature32°F to 120°F (0°C to 49°C)
Display80-character LCD
Power Supply120 VAC, 60 Hz
Capacity198 addressable devices
Notification Appliance Circuits2
Relay Contacts3 (Form-C)
Relative Humidity93% non-condensing