113
System Configuration Section 1-2
Note Power must be supplied to the Analog Output Unit from the Analog Power
Supply Unit and CQM1H/CQM1, otherwise the Analog Output Unit will not
operate.
1-2-1 Analog Power Supply Units
The following table lists the current consumptions of the Analog Output Unit
and Analog Power Supply Units. To select the Analog Power Supply Unit, refer
to the CQM1H Operation Manual (W363) or the CQM1 Operation Manual
(W226) for details.
1-2-2 CPU
The Analog Output Unit occupies two I/O words. Make sure that the total I/O
points will not exceed the I/O points of the CPU. The Power Supply Unit does
not occupy any words.
Unit Current consumption at 5 VDC (mA)
CQM1-DA021 90 mA
CQM1-IPS01 420 mA
CQM1-IPS02 950 mA