Switch Settings Section 2-2
Pin 1 Output Word Setting:
Sets the number of output words (points) occupied at the Expansion Master.
Note 1. Turn the CQM1H/CQM1 power off before setting the DIP switch. The
switch settings are enabled when the CQM1H/CQM1 power is turned on.
2. Use a different Unit number for each of the two Expansion Masters used
with a single Master.
3. Slave address for Unit 2 can only be used for an 8-point or 16-point Slave.
It cannot be used for a 4-point Slave.
Setting Description
ON One word (16 points) of outputs.
OFF Two words (32 points) of outputs.