E5EK
5--39
Event input assignment
1
Event input assignment
2
Conditions of Use
Event input other than the multi-SP func-
tion must be specified when the event
input function is in use.
• When one E53-AKB unit is mounted, only “Event input assignment 3” and
“Event input assignment 4” can be used.
• This parameter specifies event input other than the multi-SP function. The fol-
lowing three functions can be specified:
Run/Stop, Auto/Manual, SP mode.
The R emote/Local function can be used on E53-AK01/02/03 option units. The SP
mode functions can be used only when the ”Remote SP enable” parameter is ON.
• Event input (RUN/STOP, Manual/Auto, and SP mode) is disabled while the menu
is displayed.
It is also disabled in set up, expansion, option and calibration modes.
Symbol Function Event Input Operation
Not specified Event input disabled
Run/Stop ON: Stop/OFF: Run
Manual/Auto ON: Manual/OFF: Auto
SP mode ON: Remote SP/OFF: Local SP
• Default :
F Related article
4.3 How to Use Event input (page 4-8)
F Related parameters
“remote SP enable” “multi-SP function” (option mode)
F Option unit
E53-AKB
Option Mode
Function
Comment
See
Model