E5EK
5--15
Manual reset value
Conditions of Use
The control must be either standard con-
trol or advanced PID control, ST must
be set to OFF, and the “integral time”
parameter must be set to “0”.
• Sets the required manipulated variable to remove offset during stabilization of P
or PD control.
Setting Range
Unit Default
0.0 to 100.0 % 50.0
E5EK-AA2 AC100-240
E5EK-AA2 AC/DC24
Hysteresis (heat)
Hysteresis (cool)
Conditions of Use
The control system must be ON/OFF
control.
• Sets the hysteresis for ensuring stable operation at ON/OFF switching.
• In standard control, use the “hysteresis (heat)” parameter. The “hysteresis (cool)”
parameter cannot be used.
• In heating and cooling control, the hysteresis can be set independently for heati ng
and cooling. Use the “hysteresis (heat)” parameter to set the heating side hystere-
sis, and use the “hysteresis (cool)” parameter to set the cooling side hysteresis.
Parameter Setting Range
Unit Default
Hysteresis (heat) 0.01 to 99.99 %FS 0.10
Hysteresis (cool) 0.01 to 99.99 %F S 0.10
F Related article
4.1 Selecting the Control Method
/ON/OFF control (page 4 -4)
F Related parameters
“Control output 1 assignment” “Control output 2 assignment” (setup mode)
“PID / ON/OFF” (expansion mode)
E5EK-AA2 AC100-24
E5EK-AA2 AC/DC24
Level 1 Mode