CHAPTER 5 PARAMETERS
E5EK
5--16
Control period (heat)
Control period (cool)
Conditions of Use
Relay or voltage output must be set as
the outputs, and the control must be set
to advanced PID control, standard con-
trol or heating and cooling control.
• Sets the pulse output period. Set the control period taking the control characteris-
tics and life expectancy of the controller into consideration.
• In standard control, use the “control period (heat)” p arameter. The “control
period (cool)” p arameter cannot be used.
• In heating and cooling control, the control period can be set independently for
heating and cooling. Use the “control period (heat)” parameter to set the heating
side control period, and use the “control period (cool)” parameter to set the cool-
ing side control period.
Parameter Setting Range
Unit Default
Control period (heat) 1to99 Second 20
Control period (cool) 1to99 Second 20
F Related article
3.3 Setting Output Specifications (page 3 -6)
F Related parameters
“Control output 1 assignment” “Control output 2 assignment” (setup mode)
E5EK-AA2 AC100-240
E5EK-AA2 AC/DC24
Level 1 Mode
Function
Comment
See
Model