EasyManua.ls Logo

Omron E5EK - Alarm 1 type; Alarm 1 open in alarm; Alarm 2 type; Alarm 2 open in alarm

Omron E5EK
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 5 PARAMETERS
E5EK
5--30
Alarm 1 type
Alarm 2 type
Alarm 3 type
Conditions of Use
Alarms must be assigned as outputs.
For example, if alarm outputs 1 and 2
only are assigned as outputs, the “alarm
3 type” parameter cannot be used.
Alarm 1 to 3 type parameters specify the operation of the alarm by the one of
the set values in the following table. For details of operation at an alarm, see page
3-9.
Set Value Settings Set Value Settings
1 Upper-and lower-limit alarm
(deviation)
7 Lower-limit alarm with standby
sequence (deviation)
2 Upper-limit alarm (deviation) 8 Absolute-value upper-limit alarm
3 Lower-limit alarm (deviation) 9 Absolute-value lower-limit alarm
4 Upper-and lower-limit range alarm
(deviation)
10 Absolute-value upper-limit alarm with
standby sequence
5 Upper-and lower-limit alarm with
standby sequence (deviation)
11 Absolute-value lower-limit alarm with
standby sequence
6 Upper-limit alarm with standby
sequence (deviation)
Defaults: 2 (Deviation upper limit)
F Related article
3.4 Setting Alarm Type (page 3-9)
F Related parameters
Alarm value 1” Alarm value 2” Alarm value 3” (level 1 mode)
Alarm 1 hysteresis Alarm 2 hysteresis Alarm 3 hysteresis (level 2 mode)
Alarm 1 open in alarm” Alarm 2 open in alarm” Alarm 3 open in alarm” “Con-
trol output 1 assignment “Control output 2 assignment Auxiliary output 1 as-
signment” Auxiliary output 2 assignment (setup mode)
Setup Mode
Function
Comment
See

Table of Contents

Related product manuals