E5EK
5--17
Heater current monitor
Conditions of Use
The HBA output function must be
assigned.
Measures the current value of the heater from CT input.
Monitor Range Unit
0.0 to 55.0 A
[ ] is displayed when 55.0 A is exceeded.
F Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
F Related parameters
“Heater burnout” (level 1 mode) “HBA latch” (option mode)
E5EK-AA2 AC100-240
E5EK-AA2 AC/DC24
Heater burnout
Conditions of Use
The HBA output function must be
assigned.
Outputs the heater burnout alarm when the heater current value falls below this
parameter setting.
When the set value is “0.0”, the heater burnout alarm is “OFF”. When the set
value is “50.0”, the heater burnout alarm is “ON”.
Setting Range Unit Default
0.0 to 50.0 A 0.0
F Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
F Related parameters
“Heater current monitor (level 1 mode) “HBA latch” (option mode)
E5EK-AA2 AC100-240
E5EK-AA2 AC/DC24
Level 1 Mode
Function
Monitor
See
Model
Function
Comment
See
Model