E5EK
5--31
Alarm1openinalarm
Alarm2openinalarm
Alarm3openinalarm
Conditions of Use
Alarms must be assigned as outputs. For
example, if alarm outputs 1 and 2 only are
assigned as outputs, the “alarm 3 open in
alarm” parameter cannot be used.
• Selects the output states of alarms 1 to 3.
• When the controller is set to “close in alarm,” the status of the alarm output func-
tion is output as it is. When set to “open in alarm,” the status of the alarm output
function is output inverted. The following table shows the relationship between
alarm output functions, output and output LEDs.
Alarm
Output Output LED
ON ON Lit
ose
na
arm
OFF OFF Not lit
ON OFF Lit
pen
na
arm
OFF ON Not lit
Setting Range
Default
[ ] : Close in alarm/ [ ]:Open in alarm
[]
F Related article
3.4 Setting Alarm Type (page 3-9)
F Related parameters
“Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode)
“Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode)
“Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm”
“Control output 1 assignment” “Control output 2 assignment” “Auxiliary output
1 assignment” “Auxiliary output 2 assignment”(setup mode)
Direct/Reverse operation
• “Direct operation” (or normal operation) refers to control where the manipulated
variable is increased according to the increase in the process value. Alternatively,
“reverse operation” refers to control where the manipulated variable is increased
according to the decrease in the p rocess value.
Setting Range
Default
[ ] : Reverse operation/ [ ]:Direct operation []
F Related article
3.3 Setting Output Specifications/Direct/reverse operation (page 3-7)
Setup Mode
Function
Comment
See
Function
Comment
See