CHAPTER 5 PARAMETERS
E5EK
5--26
Input type
Sets the sensor type by the code.
Set the code according to the following table. Default is “2: K1 thermocouple”.
Set value Input Type
0 JPt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F)
P
l
a
t
i
n
u
m
r
e
s
i
s
t
a
n
c
e
t
h
e
r
m
o
m
e
t
e
r
1 Pt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F)
Platinum resistance thermometer
2 K1 -200 to 1300 (_C) /-300 to 2300 (_F)
3 K2 0.0 to 500.0 (_C) /0.0 to 900.0 (_F)
4 J1 -100 to 850 (_C) /-100 to 1500 (_F)
5 J2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F)
6 T -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F)
7 E 0 to 600 (_C) /0 to 1100 (_F)
8 L1 -100 to 850 (_C) /-100 to 1500 (_F)
9 L2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F)
Thermocouple
10 U -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F)
T
h
e
r
m
o
c
o
u
p
l
e
11 N -200 to 1300 (_C) /-300 to 2300 (_F)
12 R 0 to 1700 (_C) /0 to 3000 (_F)
13 S 0 to 1700 (_C) /0 to 3000 (_F)
14 B 100 to 1800 (_C) /300 to 3200 (_F)
15 W 0 to 2300 (_C) /0 to 4100 (_F)
16 PLII 0 to 1300 (_C) /0 to 2300 (_F)
17 4to20mA
C
u
r
r
e
n
t
i
n
p
u
t
18 0to20mA
Current input
19 1to5V
20 0to5V
Voltage input
21 0to10V
V
o
l
t
a
g
e
i
n
p
u
t
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameters
When input type is set to temperature input:
_C/_F selection (setup mode)
When input type is set to voltage input or current input:
“Scaling upper limit” “Scaling lower limit” “Decimal p oint” (setup mode)
Setup Mode