EasyManuals Logo

Omron E5EK User Manual

Omron E5EK
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
CHAPTER 5 PARAMETERS
E5EK
5--26
Input type
Sets the sensor type by the code.
Set the code according to the following table. Default is “2: K1 thermocouple”.
Set value Input Type
0 JPt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F)
P
l
a
t
i
n
u
m
r
e
s
i
s
t
a
n
c
e
t
h
e
r
m
o
m
e
t
e
r
1 Pt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F)
Platinum resistance thermometer
2 K1 -200 to 1300 (_C) /-300 to 2300 (_F)
3 K2 0.0 to 500.0 (_C) /0.0 to 900.0 (_F)
4 J1 -100 to 850 (_C) /-100 to 1500 (_F)
5 J2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F)
6 T -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F)
7 E 0 to 600 (_C) /0 to 1100 (_F)
8 L1 -100 to 850 (_C) /-100 to 1500 (_F)
9 L2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F)
Thermocouple
10 U -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F)
T
h
e
r
m
o
c
o
u
p
l
e
11 N -200 to 1300 (_C) /-300 to 2300 (_F)
12 R 0 to 1700 (_C) /0 to 3000 (_F)
13 S 0 to 1700 (_C) /0 to 3000 (_F)
14 B 100 to 1800 (_C) /300 to 3200 (_F)
15 W 0 to 2300 (_C) /0 to 4100 (_F)
16 PLII 0 to 1300 (_C) /0 to 2300 (_F)
17 4to20mA
C
u
r
r
e
n
t
i
n
p
u
t
18 0to20mA
Current input
19 1to5V
20 0to5V
Voltage input
21 0to10V
V
o
l
t
a
g
e
i
n
p
u
t
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameters
When input type is set to temperature input:
_C/_F selection (setup mode)
When input type is set to voltage input or current input:
“Scaling upper limit” “Scaling lower limit” “Decimal p oint” (setup mode)
Setup Mode
Function
Comment
See

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EK and is the answer not in the manual?

Omron E5EK Specifications

General IconGeneral
BrandOmron
ModelE5EK
CategoryController
LanguageEnglish

Related product manuals