6.5 How to Read Communications Error Information
E5EK
6--13
End code
14
Code name
Format error
The received command length does not match the length defined in the
frame format.
Check the communications condition. If the communications condition
of the host computer and E5EK controller match, then a probable cause
is a problem in the communications circuit of one or both of the host
computer and E5EK controller.
End code
15
Code name
Setting range error
Numerical values or code values in the data are not within the setting
range.
Check the par ameter and read or write data of special commands.
JUndefined error
CR
Unit
No.
FCS
@
*
2B
2B 2B 2B
CI
An undefined header code has been received.
A currently invalid parameter (e.g. the scaling command during tem-
perature input) has been received.
Check the parameter No.
F Description
F Action
F Description
F Action
F Description
F Action