E5EK
5--29
Auxiliary o u t p ut 1 assignment
Auxiliary o u t p ut 2 assignment
• Assigns output functions to either of auxiliary output 1 or 2.
• The following eight output functions can be assigned as outputs:
Alarms 1 to 3, HBA, LBA, Error 1 (input error), Error 2 (A/D converter error),
and Error 3 (remote SP input error).
• Control output (heat) and control output (cool) cannot be assigned as outputs.
• Error 3 can be assigned only when the remote SP function is enabled.
• When the output function assigned to auxiliary output 1 or auxiliary output 2 is
ON, the “SUB1” or “SUB2” LED lights.
Symbol
Function Alarm 1 Alarm 2 Alarm 3 HBA LBA Error 1 Error 2 Error 3
Defaults: “Auxiliary output 1”= [ ], “Auxiliary output 2”= [ ]
F Related article
3.3 Setting Output Specifications (page 3 -6)
F Related parameter
• Alarm-related p arameter
“LBA detection time” (level 2 mode)
Setup Mode
Function
Comment
See