EasyManuals Logo

Omron NS Programming Manual

Omron NS
683 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #357 background imageLoading...
Page #357 background image
Section 2 NS Series Functions 2-14 Alarms and Events
2-310
NS Series Programming Manual
General Tab Page
Sets the alarm/event display format and display conditions.
The information in the Alarm/Event Registration Dialog Box can also be read from the General Tab
Page.
1
2
3
5
6
4
7
No. Setting Details
1 Object Comment Sets an explanatory comment for the pasted object.
(Up to 32 characters.)
2 Group
specification
The display can be set to include only information from groups specified when
alarms/events are registered. Select Display only the specified group and click the Select
Button to display Select Alarm/Event Group Dialog Box.
Time and date
display format
Displays the date and time of the alarm or event. Select both Date and Time and select the
display format from the list. Refer to Date and Time Format in 2-8 Common Functional
Object Functions for information.
Switch Sets the date and time display format for each label.
Date display Selects the date display format from the list.
3
Time display Selects the time display format from the list.
4 Apply to All La-
bels
Uses the date display method for the selected label for all labels. This setting is used only
for labels for which a date display and time display are selected. Apply to All Labels cannot
be set in the following cases.
When the Date & Time Display Format Check Box is selected on the Edit/Display
Tab Page of the Option Dialog Box accessed by selecting Tools - Option.
When there is only one label.
When a date display and time display are not selected.
Movement when
Display Area is
Pressed
One of the following three operations can be selected for when the object area where the
alarm/event is displayed is pressed.
Switch
Screen to the
Specified
Page Set with
an Alarm/
Event Setting
Jumps to the page registered to the display alarm/event when the display area is pressed.
5
Switch to the
Specified
Contents set
with an
Alarm/Event
Setting
Switches the contents display to the contents set to the alarm/event displayed when the
display area is pressed.

Table of Contents

Other manuals for Omron NS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NS and is the answer not in the manual?

Omron NS Specifications

General IconGeneral
Power Supply24 VDC
Display Size5.7 to 12.1 inches (depending on the model)
Resolution320 x 240 to 800 x 600
Touchscreen TypeResistive
Display TypeTFT LCD
Communication InterfacesRS-232C, RS-422/485, Ethernet, USB
MemoryFlash memory
Operating Temperature0 to 50°C (depending on the model)
Storage Temperature-20°C to 60°C
Protection RatingIP65 (front panel)
DimensionsVaries depending on the model
WeightVaries depending on the model
CPUProprietary Omron CPU (performance varies depending on the model)

Related product manuals