Inputting from Command Buttons
1. In the numeral display and input property setting on the Keypad Tab Page, set either Input from
pop-up screen or Other Input method (e.g., Command Button) as the input method.
2. Create a Command Button with a key button function on the same screen or pop-up screen.
3. If Open pop-up screen has been specified, the specified pop-up screen will be displayed when the
numeral display and input object is pressed during operation. Command buttons inside the pop-up
screen are used to enter numerals.
4. If Other method (e.g., Command Button) is specified, numerals are entered using the command
buttons in the same screen.
Command Button Settings
1. Set Key button under the Command Button property setting on the General Tab Page.
2. Set Transmit to.
3. Set Transmit type. Select label string and set 0 to 9 and A to F to the Command Button labels to
create a button that inputs 0 to 9 and A to F like a tenkey pad. Select control code and specify a
control code to create BS and Enter Command Buttons.
Refer to Command Buttons in 2-9 Buttons for details on Command Button settings.
Inputting Decimal Fractions
Unit and scale must be set using the CX-Designer for decimal fraction input. The number of decimal
points must also be specified.
Refer to 2-8 Common Functional Object Functions for details on numeral display and input setting.
Maximum and Minimum Limits for Input
NS-series PTs can check maximum and minimum limits when setting numeral input, to ensure that il-
legal values that may affect the system are not input. Errors are prevented because an error message
is displayed if a value outside the range is input. The maximum and minimum input limits can be set
when numeral display and input objects are created using CX-Designer.
Refer to 2-8 Common Functional Object Functions for details on numeral display and input settings.
Moving Focus
In addition to moving the focus to a numeral display and input object by touching the screen, focus can
also be moved using Command Buttons.
Set Key button for the Command Button to send a control code for moving the focus. Refer to Com-
mand Buttons in 2-9 Buttons for details on Command Button settings and control codes.
Example
1234
9012 3456
5678
F RIGHT
F LEFT
HOME
F DOWN F UP
The focus can also be moved automatically to the right or down once the input has been confirmed, if
the numeral display and input object is created using the table function.
Note Always use set maximum and minimum limits to ensure the safety of numeral dis-
play and input objects.

Table of Contents

Other manuals for Omron NS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NS and is the answer not in the manual?

Omron NS Specifications

General IconGeneral
Power Supply24 VDC
Display Size5.7 to 12.1 inches (depending on the model)
Resolution320 x 240 to 800 x 600
Touchscreen TypeResistive
Display TypeTFT LCD
Communication InterfacesRS-232C, RS-422/485, Ethernet, USB
MemoryFlash memory
Operating Temperature0 to 50°C (depending on the model)
Storage Temperature-20°C to 60°C
Protection RatingIP65 (front panel)
DimensionsVaries depending on the model
WeightVaries depending on the model
CPUProprietary Omron CPU (performance varies depending on the model)

Related product manuals