H Setting a User-defined V/f Pattern (Setting “F”)
Parameters
E1-04 through E1-10 can be set by the user when E1-03 has been set to “F
.” These param
-
eters
are read-only when E1-03 isn’t set to “F
.” Parameters E1-04 through E1-10 cannot be changed
during operation.
When
making the V/f characteristics a straight line,
set the same value in E1-07 (middle output frequen
-
cy)
and E1-09 (minimum output frequency). In this case, parameter E1-08 (middle output voltage) will
be ignored.
Parameter Display name Setting Units Default
Valid access levels
*1
number
range setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E1-04 Max Frequency 40.0 to 400.0 Hz 60.0 Q Q Q Q
E1-05 Max Voltage 0.0 to 255.0
*2
VAC 200.0
*2
Q Q Q Q
E1-06 Base Frequency 0.0 to 400.0 Hz 60.0 Q Q Q Q
E1-07 Mid Frequency A 0.0 to 400.0 Hz 3.0 Q Q A ---
E1-08 Mid Voltage A 0.0 to 255.0
*2
VAC 15.0
*2,3
Q Q A ---
E1-09 Min Frequency 0.0 to 400.0 Hz 1.5 Q Q Q A
E1-10 Min Voltage 0.0 to 255.0
*2
VAC 9.0
*2,3
Q Q A ---
Note 1. Q: Quick-start, Basic, or Advanced
A: Advanced only
---: Not applicable.
Note 2. These voltages are for the 200-V class; Double the voltage for 400-V class Inverters.
Note 3. The
default
setting depends on the Inverter
’
s capacity
. The default settings shown in the table
are
for 200-V class, 0.4 to
1.5 kW Inverters. Refer to the graphs for “Setting: 1” on pages
5-26
and 5-27 for the default settings in 2.2 to 45 kW and 55 to 300 kW Inverters.
Note 4. The default settings for E1-07 through E1-10 depend on the control mode. The default
set
-
tings shown in the table are for V/f control.
Note 5. The four frequency settings must satisfy the following formula:
E1-04 (F
MAX
) ≥ E1-06 (F
A
) > E1-07 (F
B
) ≥ E1-09 (F
MIN
)
For flux vector control, make the settings as follows:
E1-04 (F
MAX
) ≥ E1-06 (F
A
) > E1-09 (F
MIN
)
User-defined V/f Pattern
Output voltage (V)
Frequency (Hz)
Basic Operation Chapter
5