EasyManua.ls Logo

Omron SYSDRIVE 3G3FV - Page 220

Omron SYSDRIVE 3G3FV
400 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-46
H Setting the Timer Function (b4)
The
timer function is enabled when the timer function input (set value: 18) and the
timer function output
(set
value: 12) are set for the multi-function input and
multi-function output respectively
. These inputs
and outputs serve as general-purpose I/O. Chattering of sensors, switches, and so on, can be pre-
vented by setting a delay time.
Parameter Display name Setting Units Default
Valid access levels
number
py
g
range setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
b4-01
Delay-ON Timer
0.0 to
300.0
Sec 0.0 Advanced
b4-02 Delay-OFF Timer 0.0 to
300.0
Sec 0.0 Advanced
These parameters cannot be changed during operation.
When
the timer function input ON time
is longer than the value set for b4-01 (timer function ON-delay
time), the timer function output turns ON.
When the timer function input OFF time is longer than the value set for b4-02 (timer function OFF-
delay time), the timer function output turns OFF.
Operation Example
Timer function input
Timer function output
ON
ON ON
ON
b4-01 b4-02 b4-01 b4-02
H Setting PID Control (b5)
The
PID control function is a control system that matches a feedback value (i.e., a de
-
tected
value) to the set target value. Combining proportional (P), integral (I), and
deriva
-
tive (D) control makes control possible even for a mechanical system with dead time.
The
PID control provided by the SYSDRIVE 3G3FV
Inverter is not suited for control that
requires a responsiveness of 50 ms or less.
This
section explains the PID control applications and operations, along
with the param
-
eter settings and tuning procedure.
Advanced Operation Chapter
6

Table of Contents

Related product manuals