EasyManua.ls Logo

Omron SYSDRIVE 3G3FV - Page 236

Omron SYSDRIVE 3G3FV
400 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-62
Parameter Display name Setting Units Default
Valid access levels
number
py
g
range setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
C6-01 Carrier Freq Max 0.4 to
15.0
(See
note.)
kHz (See
note.)
Basic or Advanced
C6-02 Carrier Freq Min 0.4 to
15.0
(See
note.)
kHz (See
note.)
Advanced ---
C6-03 Carrier Freq Gain 0 to 99 Multi-
ple
0 Advanced ---
These parameters cannot be changed during operation.
Note The
setting range and the factory default setting vary according to the Inverter
capacity
. The table
shows a value of 200-V class, 0.4 kW.
In the vector control modes, the carrier frequency is determined by the carrier frequency upper limit
(parameter C6-01).
In
the V/f control modes (both with and without PG), the carrier
frequency can be changed in response to
the
output frequency by setting the carrier
frequency lower limit (parameter C6-02) and the carrier fre
-
quency proportional gain (parameter C6-03).
The coefficient “K” varies depending on the carrier
frequency upper limit, as described below:
Carrier frequency
Output frequency
x (C6-03) x K
Output frequency
(Maximum output frequency)
E1-04
C6-01
C6-02
T
o make the carrier frequency constant, either set the same value for parameters C6-01 and C6-02 or
set the carrier frequency proportional gain (parameter C6-03) to “0” (i.e., fix at upper limit value).
The following settings will generate a parameter setting fault (OPE11):
Carrier
frequency upper limit (C6-01) > 5.0 kHz and carrier frequency lower limit (c6-02)
x
5.0 kHz
Carrier frequency proportional gain (C6-03) > 6 and (C6-01) < C6-02)
If
the lower limit is set higher than the upper limit, the lower limit
will be ignored and carrier frequency will
be fixed at the upper limit.
Note For
a 400-V Inverter
, if the carrier frequency
is set to a value higher than the default setting, the
Inverter’s
rated output current will decrease.
If the Inverter
s overload is detected earlier than the
motor overload fault (OL2), set the carrier frequency to a lower value.
Advanced Operation Chapter
6

Table of Contents

Related product manuals