6-76
Setting Description Inverters status Fault output
0 Deceleration 2: Decelerates to a stop
with C1-02 set.
Fault ON
1 Coast to a stop. Fault ON
2 Emergency stop time: Decelerates to a
stop according to the C1-09 setting.
Fault ON
3 Continuous operation. (See note.) Alarm OFF
Note If
the parameter is set to 3, the Inverter will operates without references from the host controller
.
Take necessary measures, such as emergency stop measures, to ensure safety.