6-104
Run Stall Prevention Example: L3-05 = 1 or 2
Output current
Output frequency
L3-06 (Run stall prevention level)
The output frequency is controlled
to prevent stalling.
Time
Time
H Frequency Detection Settings (L4)
Parameter Display name Setting Units Default
Valid access levels
number
py
g
range setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L4-01 Spd Agree Level 0.0 to 400.0 Hz 0.0 Basic or Advanced
L4-02 Spd Agree Width 0.0 to 20.0 Hz 2.0 Basic or Advanced
L4-03 Spd Agree Lvl+– –400.0 to
+400.0
Hz 0.0 Advanced
L4-04 Spd Agree Wdth+– 0.0 to 20.0 Hz 2.0 Advanced
Note These parameters cannot be changed during operation.
Set
these
parameters when outputting one of the frequency agree or frequency detection signals from
a
multi-function
output (settings 2, 3, 4, 5, 13, 14, 15, or 16). The following table shows the relationship
between these parameters and the output signals.
Parameter Related output settings Parameter function
Speed Agree Level
(Absolute value)
Fref/Set Agree 1 (setting 3)
Frequency Detection 1 (setting 4)
Frequency Detection 2 (setting 5)
Set the speed that you want to detect in Hz.
The set speed is an absolute value, so the
speed is detected in forward or reverse.
Speed Agree Width
(Absolute value)
Fref/Fout Agree 1 (setting 2)
Fref/Set Agree 1 (setting 3)
Frequency Detection 1 (setting 4)
Frequency Detection 2 (setting 5)
Set the speed detection range in Hz.
Speed Agree Level +/–
(Signed value)
Fref/Set Agree 2 (setting 14)
Frequency Detection 3 (setting 15)
Frequency Detection 4 (setting 16)
Set the speed that you want to detect in Hz.
Set positive values for forward, negative
values for reverse.
Speed Agree Width +/–
(Signed value)
Fref/Fout Agree 2 (setting 13)
Fref/Set Agree 2 (setting 14)
Frequency Detection 3 (setting 15)
Frequency Detection 4 (setting 16)
Set the speed detection range in Hz.
Set
the corresponding setting in the multi-function output (H2-01, H2-02, or
H2-03) to output the de
-
sired
Fref/Fout Agree signal, Fref/Set Agree signal, or Frequency Detection signal. There is a
timing
chart showing the operation of these signals on the following page.