7-6
Para
meter
No.
PageControl
mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
DescriptionNamePara
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
b1-05
Operation
Selection
for
Minimum
Frequency
(E1-09 or
less)
Used to set the method of
operation when the frequency
reference input is less than the
minimum frequency (E1-09).
0:
Run at frequency reference
(E1-09 not ef
fective).
1: ST
OP (Frequencies below
E1-09 in the coast to stop
state.)
2:
Run at min. frequency
.
(E1-09)
0 to 3
0 NO X X X A 5-33
Zero-Speed
Oper
3:
Run at zero speed
(Frequencies below E1-09
are zero)
Note:
This function is only avail
-
able in with flux vector
control.
b1-06
Setting
Control In
-
put Re
-
sponsive-
ness
Used to set the responsiveness
of the control inputs
(forward/reverse and
multi-function inputs.)
0: Two scans every 2 ms (Use
when connecting transistor
0, 1
1 NO A A A A 5-11
Cntl Input
Scans
outputs.)
1: Two scans every 5 ms (Use
when connecting contact
outputs or switches.)
b1-07
Operation
Selection
After
Switching
to Remote
Mode
Used to set the Operation mode
by switching to the Remote
mode using the Local/Remote
Key.
0:
Run signals that are input
during mode switching are
ignored. (Input Run signals
after switching the mode.)
0, 1
0 NO A A A A ---
LOC/REM
RUN Sel
1:
Run signals become
ef
fective immediately after
switching to the Remote
mode.
b1-08
Operation
for run
commands
in modes
other than
drive mode
Used to set the operation when
a run command is input in a
mode other than drive mode.
0:
Run command inef
fective
(Ignore run command.
Switch to drive mode and
input the run command
again in order to run.)
1:
Run command ef
fective
(Run according to run
0, 1
0 NO A A A A 6-41
RUN CMD
at PRG
command.)
Note:
Safety precautions are re
-
quired when using the “1”
setting.
Note:
The “1” setting is not valid
if b1-02 = 0.
Parameter Lists Chapter
7