7-26
Para
meter
No.
PageControl
mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
DescriptionNamePara
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
E1-11
Mid. Output
Frequency
B
Used to set the middle
frequency and voltage in the
constant output area. Normally
,
this setting is not required.
0.0 to
400.0
0.0 NO A A A A ---
Mid
frequency
B
Note:
When using a high-speed
motor
, set the characteris
-
tics of the constant output
area.
E1-12
Mid. Output
Frequency
V
oltage B
Output voltage (V)
VMA
E1-05
E1-12
E1-13
0.0 to
255.0
(See
note 1.)
0.0 NO A A A A ---
Mid voltage
B
0
FA
E1-06
E1-11 FMAX
E1-04
E1-13
Base
Voltage
Frequency (Hz)
Note: Set
as follows:
E1-06<E1-11<E1-O4.
0.0 to
255.0
(See
0.0 NO A A Q Q ---
Base
voltage
.
Note:
This parameter becomes
disabled if E1-1
1 and
E1-12 are set to “0.”
note 1.)
Note 1. These
are values for a 200-V class Inverter
. Double these values for a 400-V class Inverter
.
Note 2. When the control mode is changed, the Inverter reverts to default settings. (The open loop
vector control default settings are given above.)
H Motor Setup: E2
Para
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
E2-01
Motor rated
current
Sets the motor rated current in
1-A units.
Note:
These set values will be
-
come the reference val
-
ues for motor protection,
0.32 to
6.40
(See
note 2.)
1.90
(See
note 1.)
NO Q Q Q Q 5-23,
5-44,
6-9,
6-32
Motor
Rated FLA
torque limits and torque
control.
These values will auto
-
matically be set if they
were set during auto-tun
-
ing.
E2-02
Motor rated
slip
Sets the motor rated slip in Hz
units.
Note:
These set values will be
-
come the reference val
-
0.00 to
20.00
2.90
(See
note 1.)
NO A A Q Q 6-10,
6-15,
6-32
Motor
Rated Slip
-
ues for slip compensation.
These values will be auto
-
matically set if auto-tuning
is started.
E2-03
Motor
no-load
current
Sets the motor no-load current
in 1-A units.
Note:
These values will be auto
-
0.00 to
2.9
(See
1.20
(See
note 1.)
NO A A Q Q 6-10,
6-15,
6-32
No-Load
Current
matically set if auto-tuning
is started.
Parameter Lists Chapter
7