7-48
Para
meter
No.
PageControl
mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
DescriptionNamePara
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
L4-05
Operation
when
frequency
reference is
lost
0: Stop (Operation follows the
frequency reference.)
1: Operation at 80% speed
continues. (At 80% of speed
before the frequency reference
was lost)
0, 1
0 NO A A A A 6-105
Ref Loss
Sel
Note:
Frequency reference is
lost: Frequency reference
dropped over 90% in
400 ms.
H Fault Restart: L5
Para
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
L5-01
Number of
auto restart
attempts
Sets the number of auto restart
attempts. Automatically restarts
after a fault and conducts a
0 to 10
0 NO B B B B 6-107
Num of
Restarts
speed search from the run
frequency.
L5-02
Auto restart
operation
selection
Sets whether a fault contact
output is activated during fault
restart.
0:
Not output (Fault contact is
0, 1
0 NO B B B B 6-107
Restart Sel
not act
1:
Output (Fault contact is
activated.)
H Torque Detection: L6
Para
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
L6-01
Torque
detection
selection 1
0:
Overtorque detection
disabled.
1:
Detection during speed
agree only/Operation
continues after detection
(Minor fault)
2:
Detection during
run/Operation continues
after detection (Minor fault)
0 to 4
0 NO B B B B 6-108
T
orq Det 1
Sel
a
3:
Detection during speed
agree only/Inverter output is
shut of
f after detection
(Fault)
4:
Detection during
run/Inverter output is shut
of
f after detection (Fault)
L6-02
Torque
detection
level1
V
ector control: Motor rated
torque is set as 100%.
V/f control: Inverter rated output
0 to
300
150 NO B B B B 6-108
T
orq Det 1
Lvl
current is set as 100%.
Parameter Lists Chapter
7