EasyManuals Logo

PREVOST X3-45 Multiplex User Manual

PREVOST X3-45 Multiplex
1422 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #189 background imageLoading...
Page #189 background image
3
Figure 4 - TESTING PINION MOVEMENT AND PULL-
IN WINDINGS (GROUND-FLOAT TYPE)
For the starter switch coils, refer to the
switch circuit diagrams for the ground-wire
type (ground-float type) shown in figures 5.
Figure 5 - SOLENOID CIRCUIT (GROUND-FLOAT
TYPE)
If the pinion is performing properly, follow
the procedure as described below to inspect
the H-coil in the starter solenoid.
Remove the M-terminal nut as described in
figure 6 and keep the lead wire end in
contact with the M-terminal. Apply voltage
between the S-terminal and the ground to let
the pinion advance forward. Immediately
after that, separate the lead wire from the M-
terminal and check if the pinion stays in the
advanced forward position while voltage is
applied to the H-coil only. If the pinion
returns, replace the starter. The H-coil is
assumed to be layer-shorted.
* M-terminal nut tightening torque: 20 to 30
Nm
Figure 6 - TESTING HOLD-IN WINDINGS (GROUND-
FLOAT TYPE)
Below are the resistance values for the P-
and H-coils for reference.
Coil Resistance (reference)
P-coil
0.072ohm at 68° F
H-coil
1.300 ohm at 68° F
2.5.2 No-load test
The no-load test makes it easy to inspect
the starter for functional failure without
disassembling. This test can also identify an
open/short circuit that is difficult to check
when disassembled.
As shown in figure 7, connect the starter,
fully charged battery, ammeter, and
voltmeter. If possible, connect a resistor
suitable for voltage control in parallel with
the battery. In addition, use an rpm indicator
to measure the revolution speed of the
output shaft.
Note:
Attention should be given to the
output shaft which advances forward to
approximately 0.8" (20 mm) and rotates at
that position when the starter is operated.
Figure 7 - NO-LOAD TEST CIRCUIT (BODY-
GROUND TYPE)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PREVOST X3-45 Multiplex and is the answer not in the manual?

PREVOST X3-45 Multiplex Specifications

General IconGeneral
Length45 ft
Width102 in
EngineVolvo D13
Horsepower500 hp
GVWR54, 000 lbs
Height146 in
Sleeping CapacityVaries based on floor plan
Water CapacityVaries based on floor plan

Related product manuals