EasyManuals Logo

REXROTH IndraDrive C User Manual

REXROTH IndraDrive C
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #159 background imageLoading...
Page #159 background image
Rexroth IndraDrive Requirements to the Mains Connection 10-21
DOK-INDRV*-SYSTEM*****-PR02-EN-P
Insulation Monitoring Devices
Insulation monitoring devices are normally used in IT mains with insulated
neutral point. The aim is to have a monitor triggered in the case of ground
fault - i.e. in the case of error - without having to switch off the electrical
equipment.
When the monitor signals an error, the ground fault is detected and
removed without operation being switched off. Switch-off only takes place
if a second ground fault occurs before the first one has been removed.
As insulation monitoring devices are also measuring the ground current at
the mains input of the building, too high leakage current can cause
accidental false triggering.
There are the same notes on application applying as mentioned in the
previous section "Use of Residual-Current-Operated Circuit-Breakers
(RCCB, RCD) as Additional Fusing".

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the REXROTH IndraDrive C and is the answer not in the manual?

REXROTH IndraDrive C Specifications

General IconGeneral
Protection ClassIP20
Voltage Range200 V to 480 V
Input Voltage200 to 480 VAC
Control ModesSpeed, Torque, Position
Communication InterfacesPROFIBUS, CANopen, Ethernet
Feedback SystemsResolver, incremental encoder, absolute encoder

Related product manuals