Rexroth IndraDrive Brief Description, Applications 4-1
DOK-INDRV*-SYSTEM*****-PR02-EN-P
4 Brief Description, Applications
In terms of "Appropriate Use", cases of operation and applications not
mentioned in this chapter are not allowed.
4.1 Applications of the Drive System Rexroth IndraDrive
The digital intelligent automation system Rexroth IndraDrive is the cost-
efficient solution with a high degree of functionality for single-axis and
multi-axis drive and control tasks.
The IndraDrive automation system can be used for realizing a large
number of drive tasks in the most varied applications.
Typical applications are the industrial sectors
• printing and paper converting
• packaging and food
• mounting and handling
• wood machining
• machine tools
• metal forming
• general automation
For these applications there are different device types of graduated
performance available.
4.2 Mains Transformers DST and DLT
Applications
DST and DLT transformers are used to
• transform mains voltages to the allowed nominal voltage of the device
DLT transformers are used to
• prevent overvoltage between outer conductor and ground
• keep away leakage currents from other loads
Device type Application
DST autotransformer
adjusting voltage range in grounded
mains
DLT isolating transformer adjusting voltage range in
ungrounded mains
Fig. 4-1: Transformer applications
Note: As a matter of principle, DLT isolating transformers have to be
used at ungrounded mains.
Applications